Customization: | Available |
---|---|
Kind: | New-Type Transmitter |
Type: | AC Transmitter |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
An : Current input | An rating range |
A1 1 A 0 - 1.5 A |
A2 5A 0 - 7.5 A |
A3 10A 0 - 15 A |
Ay Specified |
On : Output | ||
O1 0 - 1 mA |
O2 0 - 20 mA |
O3 4 - 20 mA |
||||||
O4 0 - 1 V |
O5 0 - 5 V |
O6 0 - 10 V |
||||||
Pn : Auxiliary power | Pn rating range |
P1 AC120 V 120 V ± 15% |
P2 AC240 V 240 V ± 15% |
Ps Internal Power |
Py Specified |
|||
O7 2 - 10 V |
Oy Specified |
Accuracy(23±3°C) | 0.1% RO | |
Maximum output load | DC current mode : maximum 10V drop DC voltage mode : maximum 5mA drive |
|
Dielectric strength | AC 2KV 1 minute between terminals: Ac 2.6KV 1 minute / terminals to case | |
Surge and impulse test | ANSI C37.90/1989, IEC 255-3(1989) 4KV 1.2 x50us | |
Maximum input over | Current related input | |
1A/ 5A | 10A | |
4 x rated / continuous | 2 x rated /continuous | |
10 x rated / 10 seconds | 25 xrated /1 second | |
50 x rated /1 second | 50 x rated /0.5 second | |
80 x rated /0.5 second | ||
Input burden | Less 0.2 VA | |
Response time & ripple | ≤ 400 ms for step change 0-99% ripple less 0.5% ro peak to peak | |
Frequency | 45~ 400 Hz | |
Stability | Temperature range (20 to 30°C) long term stability / year Maximum 60 ppm / °C less 0.2% draft / year typically |
|
Storage condition | Temperature range -25 to 70°C, RH 20 to 95% non condensed | |
Operating condition | Temperature range -20 to 65°C, RH 0 to 99% non condensed | |
Magnetic field effect | <0.01% under 100 ampere turns at 1M center | |
Power dissipation | Maximum 3.5 VA |
LPAX