Juxta Combination Watt/Var Transducers

Kind: Two-wire Transmitter
Type: AC Transmitter
Phase: Three
Wire-Assembly Type: Four-wire Transmitter
Accuracy Grade: 0.2G
Certification: ISO
Customization:
Diamond Member Since 2023

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
248943-540-AHD-0-M
Customized
Customized
Trademark
jinhan
Origin
China
HS Code
9030339000
Production Capacity
5000

Product Description

JUXTA COMBINATION WATT/VAR TRANSDUCERS
1.GENERAL
The 2469 and 2489 combined WATT/VAR transducers produce an analog output equal to the WATTS and
VARS measured by the input. .

2.SPECIFICATIONS:
Model #   2469 2489
Current input / range 0-1 Amp AC or 0-5 Amp AC
10 to 200% of rated input 0-200% of rated input
Current input over range capability 200% of rated input continuous
1000% of rated input for 5 seconds
Current input burden < 0.2VA per element
Voltage inputs and range: Input powered range
Auxiliary powered range
Voltage input burden per element
120V 240V
100-135VAC 200-264VAC
0-120% rated input
< 0.5VA < 1.0VA
120V 240V
85-135VAC 170-264VAC
0-120% of rated input
< 0.3VA < 0.6VA
Sustained Voltage input overange 150% of rated input without damage (Auxiliary powered only)
Rated outputs 0 to ±1mADC into a 10kW max. load; 10VDC output compliance
4-20 mADC into 750W max. load; 15VDC output compliance
Accuracy ±0.5% of full scale
±0.5% of full scale
±0.5% of span
± 0.1% of reading. ± 0.05% full scale
± 0.1% of reading. ± 0.1% full scale
± 0.2% of span
Output calibration / element Zero: ± 1% minimum
Span: ± 2% minimum
Zero: ± 5% minimum
Span: ± 10% minimum
External calibration adjustment < 400 milliseconds (0-99% of output)
Response time 0.3% of span peak-to-peak max. 0.5% of span peak-to-peak max.
Output ripple 2500 VAC input to output, power and case 2000 VAC aux. power to output and case
500 VAC output to case
Isolation IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds)
Surge Withstand Capability > 10 megohm / 500VDC input/output/power/case
Insulation resistance -20°C to +60°C
Operating temperature 0 - 90% relative humidity (non-condensing)
Operating humidity ±250 PPM / °C of span 1mA = W ± 50FS, V ±75span (PPM/°C)
Temperature effect < 0.2% at 400 AT/m
External magnetic field <0.5% <0.2%
Influence  :  unbalanced  currents  /
phase  interaction  / Power Factor
<0.25%, 45-65 Hz, fundamental through 9th harmonic (Watt only)
Weight 1200g (2.65 lbs.)
Shock <0.2% after 50G, 3 Axis and 6 repetitions
Vibration <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis
UL Recognition File # E60579
3) STANDARD MODELS
120 VAC, 5AAC, 60 Hz, input powered 2469 (0.5% Accuracy) 2489 (0.2% Accuracy)
W/V 1P2W, 0±1mA output (1 Element)
W/V 1P2W, 4-20mA output (1 Element)* W/V 3P3W, 0±1mA output (2 Element)
W/V 3P3W, 4-20mA output (2 Element)*
W/V 3P4W, 0±1mA output (212  Element)
W/V 3P4W, 4-20mA output (212  Element)*
W/V 3P4W, 0±1mA output (3 Element)
W/V 3P4W, 4-20mA output (3 Element)*
246941-540-AFB-0-M 248941-540-AFB-0-M
246941-540-AHD-0-M 248941-540-AHD-0-M
246943-540-AFB-0-M 248943-540-AFB-0-M
246943-540-AHD-0-M 248943-540-AHD-0-M
246944-540-AFB-0-M 248944-540-AFB-0-M
246944-540-AHD-0-M 248944-540-AHD-0-M
246945-540-AFB-0-M 248945-540-AFB-0-M
246945-540-AHD-0-M 248945-540-AHD-0-M
NOTE: See order format on next page for additional ratings, frequency calibrations, power-up and output options.
*VAR outputs for "AHD" are 12±8 mADC (see output options on next page). Auxiliary power supply options <5.0 burden.