Basic Info.

Model NO.
JA866-AI
Material
Plastic
Accuracy Grade
0.2G
Certification
ISO
Customized
Customized
Transport Package
Independent Carton Package
Trademark
jinhan
Origin
Zhejiang China
HS Code
9030849000
Production Capacity
5000

Product Description

Application

Used for measurement of active power, reactive power and output of an isolated analog signal
 
Technical Data
 
Accuracy Class: 0.5 ,0.2.Class 0.5%RO,Class 0.2%RO.
Input:
Nominal Value: Current: AC 1A,5A;
:AC Voltage: 100V,220V,380V,450V,57.7V.
Overload Current: 1.2,10/1
Continuous 120% of rated, 10 times of rated current of duration of 1s
:
Individual absorption power
≤0.3VA();≤1W(400V)
≤ 0.3VA (current input); less than 1W (400V voltage  input)
Frequency: 50Hz,60Hz,±5%
Output:
Nominal value 4~20mA
Load Resistance 50~300Ω;For Current output:  50~300Ω
Ripple content <0.5%;<0.5% peak value;
Response time ≤400ms
Power supply:
Voltage: AC/DC 85~260V
Power consumption: ≤3VA
Insulation resistance: ≥100MΩ
Dielectric Strength: // 2.0kV/1min,50Hz
50Hz 2.0kV/1min between input and output and power supply
Temperature coefficient: 0ºC~+60ºC,≤100PPM/ºC;When 0ºC~+60ºC, ≤100PPM/ºC
Working ambient:
Temperature: :-10~+55ºC :-25~+70ºC;Working: -10~+55ºC storage: -25~+70ºC
Humidity: ≤90%RH,,;≤ 90%RH, No condensation and corrosive gas
Altitude: ≤2500m
Installation mode: TS35;TS35 Rail
 
Main product model

AC Current Transducer: JA866-AI; 

AC Voltage Transducer: JA866-AU, 
Frequency Transducer: JA866-H;
Single Phase Power Factor Transducer: JA866-PF; 
hree-phase Power Factor Transducer: JA866-PF3;
DC Voltage Transducer: JA866-DU; 
DC 75mV Transducer: JA866-DI;
3φ3W Active Power Transducer:JA866-3P        
3φ3W Reactive Power Transducer:JA866-3Q
3φ3W active power&reactive &current power Transducer:JA866-3P/Q/I
3φ4W Active Power Transducer:JA866-4P
3φ4W Reactive Power Transducer:JA866-4Q
3φ4W active power&reactive power Transducer:JA866-4P/Q    
Three-phase Current transducer:JA866-3I 
3φ3W Voltage transducer: JA866-3U
3φ4W Voltage transducer:JA866-4U




 
Outline dimension

Ja866 Series Power TransducerJa866 Series Power Transducer
 
Detailed Photos
Ja866 Series Power Transducer
Ja866 Series Power Transducer
Ja866 Series Power Transducer
Ja866 Series Power Transducer
Ja866 Series Power Transducer

 


























 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier