Model # | 2469 | 2489 | |
Current input / range | 0-1 Amp AC or 0-5 Amp AC | ||
10 to 200% of rated input | 0-200% of rated input | ||
Current input over range capability | 200% of rated input continuous 1000% of rated input for 5 seconds |
||
Current input burden | < 0.2VA per element | ||
Voltage inputs and range: Input powered range Auxiliary powered range Voltage input burden per element |
120V 240V 100-135VAC 200-264VAC 0-120% rated input < 0.5VA < 1.0VA |
120V 240V 85-135VAC 170-264VAC 0-120% of rated input < 0.3VA < 0.6VA |
|
Sustained Voltage input overange | 150% of rated input without damage (Auxiliary powered only) | ||
Rated outputs | 0 to ±1mADC into a 10kW max. load; 10VDC output compliance 12±8mADC into a 750W max. load; 15VDC output compliance |
||
Accuracy | 0 ± 1mADC = ±0.5% of full scale 12±8mADC = ±0.5% of span |
0±1mADC = ±0.1% rdg. ± 0.1%FS 12±8mADC = ±0.2% of span |
|
Output calibration / element | 120VAC: 1 Amp = 0-100 VARS; 5 Amp = 0-500 VARS 240VAC: 1 Amp = 0-200 VARS; 5 Amp = 0-1000 VARS |
||
External calibration adjustment | Zero: ± 1% minimum Span: ± 2% minimum |
Zero: ± 5% minimum Span: ± 10% minimum |
|
Response time | < 400 milliseconds (0-99% of output) | ||
Output ripple | 0.3% of span peak-to-peak max. | 0.5% of span peak-to-peak max. | |
Isolation | 2500 VAC input to output, power and case 2000 VAC aux. power to output and case 500 VAC output to case |
||
Surge Withstand Capability | IEEE472/ANSI C37.90.1 - 1989, JIS C1111 (5KV 1.2 x 50 microseconds) | ||
Insulation resistance | > 10 megohm / 500VDC input/output/power/case | ||
Operating temperature | -20°C to +60°C | ||
Operating humidity | 0 - 90% relative humidity (non-condensing) | ||
Temperature effect | ±250 PPM / °C of span | 1mA ±50FS, 4-20mA ±80span (PPM/°C) | |
External magnetic field | < 0.2% at 400 AT/m | ||
Influence : unbalanced currents / phase interaction / Power Factor |
<0.5% | <0.2% | |
Weight | 1200g (2.65 lbs.) | ||
Shock | <0.2% after 50G, 3 Axis and 6 repetitions | ||
Vibration | <0.2% after 16.7 Hz, 4 mmp-p 1 hour, 3 Axis | ||
UL Recognition | File # E60579 |
120 VAC, 5AAC, 60 Hz, input powered | 2469 (0.5% Accuracy) | 2489 (0.2% Accuracy) |
VAR 1P2W, ±1mA output (1 Element) VAR 1P2W, 12±8mA output (1 Element) VAR 3P3W, ±1mA output (2 Element) VAR 3P3W, 12±8mA output (2 Element) VAR 3P4W, ±1mA output (21⁄2 Element) VAR 3P4W, 12±8mA output (21⁄2 Element) VAR 3P4W, ±1mA output (3 Element) VAR 3P4W, 12±8mA output (3 Element) |
246961-540-AFB-0-M | 248961-540-AFB-0-M |
246961-540-AHF-0-M | 248961-540-AHF-0-M | |
246963-540-AFB-0-M | 248963-540-AFB-0-M | |
246963-540-AHF-0-M | 248963-540-AHF-0-M | |
246964-540-AFB-0-M | 248964-540-AFB-0-M | |
246964-540-AHF-0-M | 248964-540-AHF-0-M | |
246965-540-AFB-0-M | 248965-540-AFB-0-M | |
246965-540-AHF-0-M | 248965-540-AHF-0-M |